Hazardous Area Classification (HAC) Study as per NFPA

Q1.What is the Objective of HAC? 

A1. The objective of HAC is as follows:

The purpose of the Hazardous Area Classification study is to determine the extent of the hazardous areas around equipment handling or storing  flammable fluids, combustible fluids and combustible dusts, both liquid and  vapors in  terms of Zone0, Zone 1, Zone 2 and Division 1 and Division 2  

The aim of hazardous area classification is to avoid ignition of those releases  that may occur from time to time in the operation of facilities handling  flammable liquids and vapors.  The approach is to reduce to an acceptable  minimum level the probability of coincidence of a flammable atmosphere and an  electrical or other source of ignition occurring. In Hazardous Area  Classification the extent of the hazardous areas around equipment handling  or storing flammable  fluids, both liquid and vapors is determined  in  terms  of Zone 0, Zone 1, and Zone 2. The hazardous area  classification around  the equipment handling flammable/explosive dust is  determined in terms  of  Division 1, Division 2. 

Q2.What is the Scope of HAC? 

A2. The Scope of HAC is as follows:

The Hazardous area classification is carried out as per:

  • Classification of the Hazardous area for explosive dust is carried out  as per NFPA 499  
  • Classification of the Hazardous area for flammable liquids/ gases/ vapors  is carried out by NFPA 497 

Q3.What reference is commonly used for HAC Study? 

A3. The reference used for HAC study is as follows:

  • NFPA 497 Classification of Flammable Liquids, Gases, or Vapors and of  Hazardous(Classified) Locations for Electrical Installations in Chemical  Process Areas. 
  • NFPA 499 (Classification of Combustible Dusts and of Hazardous  (Classified) Locations for Electrical Installations in Chemical Process Areas) 

Q4.What is the order of precedence for HAC Study? 

A4. The order of precedence for HAC study is as follows:

  • NFPA 497/ NFPA 499 
  • As per Client Guidelines 
  • Other international standards

Q5.What is the methodology for HAC Study?

A5. The methodology for HAC Study is as follows:

  • Data collection 
  • MSDS Sheet Preparation 
  • Process step and Representative Chemical sheet preparation  
  • Client Approval for HAC Schedule preparation  
  • HAC Schedule 
  • Draft Report 
  • Client Approval for HAC marking  
  • HAC marking  
  • Comments incorporation along with CRS (Comment Resolution Sheet)  
  • Final Report 

Q6.Different Types of Grade of Release?

A6. Three types of grade of release are as follows:

  • Continuous Grade release (C): A release that is continuous or  nearly  so , or that occurs frequently and for short periods. 
  • Primary Grade release (P): A release that is likely to occur periodically or  occasionally in normal operation, that is, a release which, in operative  procedures, is anticipated to occur. 
  • Secondary grade release (S): A release that is unlikely to occur in normal  operation and, in any event, will do so only infrequently and for short  periods, that is, a release which, in operating procedures, is not anticipated to  occur.

Q7.Different Types of Class of the Fluid?

A7. Three types of class of fluid are as follows:

  • Flammable Liquids vary in volatility and have a flash point below 93° C  and a Vapor Pressure not  exceeding 2.81 kg/cm2  at 37.8° C.  These are divided  into  three classes, as follows, 
  • Class A :  Flammable liquids having flash point below 23° C 
  • Class B :  Flammable liquids having flash point 23° C and above but below  65°C
  • Class B :  Flammable liquids having flash point 23° C and above but below  65°C

Q8.Area Classification (As per NFPA 497)? 

A8. Area classification as per NFPA is as follows:

  • Class1 Zone 0 Areas: A Class I, Zone 0 location is a location that meets the  following conditions: 
  • Ignitable concentrations of flammable gases or vapors that are present  continuously 
  • Ignitable concentrations of flammable gases or vapors that are present for  long periods of time. 
  • Class I, Zone 1. Areas: A Class I, Zone 1 location is a location that meets  the following conditions:  
  • Ignitable concentrations of flammable gases or vapors that are likely to  exist under normal operating conditions. 
  • Ignitable concentrations of flammable gases or vapors that may exist  frequently because of repair or maintenance operations or because of  leakage. 
  • Class I, Zone 2 Areas: A Class I, Zone 2 location is a location that meets the following conditions:  
  • Ignitable concentrations of flammable gases or vapors that are not  likely to occur in normal operation, and if they do occur, they will  exist only for a  short period.  

Q9.What is the steps for HAC  Study? 

A9. The steps for HAC Study are as follows:

Methodology NFPA for Flammable liquid and vapors

  • Review Process Flow diagram  
  • Prepare separate table for liquid and solid chemical along With flammable /combustible Properties 
  • Classification of material as per NFPA-497 
  • Selecting the Appropriate Classification Diagram 
  • Determine the Zone classification  
  • Determine Extent of the Classified Location  
  • Review and recommendation  

To enable selection of electrical equipment appropriate to the zone  classification, the apparatus sub group and temperature class is then  determined based on the flammable substances that can be release. 

Methodology for Combustible dusts  

  • Need For Classification 
  • Facility information & history 
  • Classification of material as per NFPA-499 
  • Selecting the Appropriate Classification Diagram 
  • Determine the Zone classification  
  • Determine Extent of the Classified Location  
  • Review and recommendation  

To enable selection of electrical equipment appropriate to the zone  classification, the apparatus sub group and temperature class is then  determined based on the flammable substances that can be release. 

Q10.What are the documents required for the HAC Study? 

A10. The documents required for the HAC Study include the following:

  • Scope of work 
  • Approved P&IDs 
  • List of Chemicals 
  • Process design basis 
  • Hazardous inventories and their SDS 
  • Process description 
  • MSDS or Chemical properties of RM & FG 
  • Equipment Design and Operating Condition /MOC  
  • Equipment’s & Details 
  • Layout & plot plan 

Q11.What are documents deliverables for HAC Study?

A11. The documents deliverables for HAC Study are as follows:

  • Executive Summary 
  • Document Review 
  • Submission of terms of reference 
  • HAC Methodology 
  • HAC Schedule 
  • HAC Marked Layout  
  • Comments Resolution sheets 
  • Reference 
  • List of tables 
  • List of appendix 

Q12.Which software will be used for the HAC study? 

A12. Following software will be used for HAC marking:

  • AutoCAD 

Q13.Different guidelines for HAC study? 

A13. Different guidelines used for HAC study are as follows:

  • IEC 60079-10-1 Explosive atmospheres Part 10-1: Classification of areas –  Explosive gas atmospheres 
  • IEC 60079-10-2 Explosive atmospheres Part 10-2: Classification of areas –Explosive dust atmospheres 
  • Draft Version of EI15 Edition 4Model Code of Safe Practice – Area  Classification Code for Installations Handling Flammable Fluids. Energy  Institute 2015. 3. 
  • EI15 Edition 3 Model Code of Safe Practice – Area Classification Code for  Installations  Handling Flammable Fluids. Energy Institute 2005. 
  • IS 61241- “Electrical Apparatus for Use in the Presence of Combustible Dust – Code of Practice” 
  • IS 5572- “Code of Practice for Electrical Installations of Industrial  Establishments: Part 1 General Aspects” 

Q14.Graphical representation of Different Zones of HAC? 

A14. Graphical representation of HAC Zones are as follows:

Q15.What is the Comment Resolution Sheet?  

A15. The meaning of Comment Resolution Sheet (CRS) is as follows:

A comment resolution sheet is a document used to track and address comments, feedback, or issues raised during a review process, audit, or evaluation.

DISCLAIMER

This Blog is provided solely for informational and educational purposes. It is advisable to verify all information presented and consult with appropriate experts or professionals before making any decisions or implementing any strategies based on the content of this blog. HSE Risk Management Services Pvt. Ltd. accept no liability for any actions taken or not taken based on the information provided herein.